600Volt.Copper Conductor, XHHW-2 as Inners
Cross-linked Polyethylene (XLPE) Insulation
Sunlight Resistant PVC Jacket
Service Entrance Cable with Bare Neutral
APPLICATIONS
SE-R (Service Entrance Cable Style R) is used to convey power from the service drop to the meter base and from themeter base to the distribution panelboard; however, it may be used in all applications where SE-Rcable is permitted. SE-Rmay be used in wet or dry above ground locations at temperatures not to exceed 90°C. The voltage rating is 600 volts.
STANDARDS
Morn’s SE-RCable with XHHW-2complies with:
•ASTMB3, B8
•UL 44(UL83/UL854)
CONSTRUCTION
Conductor |
|
||
Insulation |
•Cross-linked polyethylene (XLPE) insulation meeting the required thickness of Type XHHW-2 rated for 90°C in wet or dry locations |
||
Ground |
• Bare Stranded compressed soft-annealed uncoated copper |
||
Bedding |
•Glass-reinforced polyester tape bedding |
||
Jacket |
• Sunlight resistantPolyvinylchloride (PVC) jacket, |
TECHNICAL PARAMETER LIST
Size/ Construction (AWG or kcmil) |
Numberof Strands |
O.D. (mils) |
Approxi. Weight per 1000' (lbs) |
Allowable Ampacities (Amps) |
||||
Phase Conductors |
Ground Conductor |
60°C |
75°C |
90°C |
Dwelling |
|||
SE-R Two Conductor with Bare Ground (Formerly referred to as "Three Conductor") |
||||||||
8-8-8 |
7 |
7 |
510 |
209 |
40 |
50 |
55 |
/ |
6-6-6 |
7 |
7 |
600 |
338 |
55 |
65 |
75 |
/ |
7 |
7 |
710 |
474 |
70 |
85 |
95 |
100 |
|
2-2-2 |
7 |
7 |
840 |
716 |
95 |
115 |
13 |
125 |
1/0-1/0-1/0 |
19 |
19 |
1114 |
1169 |
125 |
150 |
170 |
175 |
2/0-2/0-2/0 |
19 |
19 |
1060 |
1117 |
145 |
175 |
195 |
200 |
4/0-4/0-4/0 |
19 |
19 |
1380 |
2145 |
195 |
230 |
260 |
250 |
SE-R Three Conductor with Bare Ground (Formerly referred to as "Four Conductor") |
||||||||
8-8-8-8 |
7 |
7 |
580 |
275 |
40 |
50 |
55 |
/ |
6-6-6-6 |
7 |
7 |
690 |
416 |
55 |
65 |
75 |
/ |
4-4-4-6 |
7 |
7 |
790 |
567 |
70 |
85 |
95 |
100 |
2-2-2-4 |
7 |
7 |
935 |
872 |
95 |
115 |
130 |
125 |
1-1-1-3 |
19 |
7 |
1050 |
1100 |
110 |
130 |
150 |
150 |
1/0-1/0-1/0-2 |
19 |
19 |
1135 |
1363 |
125 |
150 |
170 |
175 |
2/0-2/0-2/0-1 |
19 |
19 |
1282 |
1683 |
145 |
175 |
195 |
200 |
3/0-3/0-3/0-1/0 |
19 |
19 |
1384 |
2096 |
165 |
200 |
225 |
225 |
4/0-4/0-4/0-2/0 |
19 |
19 |
1483 |
2602 |
195 |
230 |
260 |
250 |
NOTE: Other conductor sizes are available upon request.
CopyRight©2012-2013 Shanghai Morn Electric Equipment Co.,Ltd All Rights 沪ICP备2022033776号
Reserved Lingang factory address:
No.2829 Jiangshan Road, Pudong New Area, Shanghai, China
Tel:+86-21-68099820 Fax:+86-21-58975163