600Volt.Copper Conductors, XHHW-2 as Inners,
Cross-linked Polyethylene (XLPE) Insulation
Sunlight Resistant PVC Jacket
Service Entrance Cable with Concentric Neutral
APPLICATIONS
SE-U (Service Entrance Cable Style U) is used to convey power from the service drop to the meter base and from themeter base to the distribution panelboard; however, it may be used in all applications where SE-U is permitted. SE-Umay be used in wet or dry above ground locations at temperatures not to exceed 90°C. The voltage rating is 600 volts.
STANDARDS
Morn’sSE-U CU Cable complies with:
•ASTMB3, B8
•UL 44(UL83/UL854)
CONSTRUCTION
Conductor |
|
||
Insulation |
•Cross-linked polyethylene (XLPE) insulation meeting the required thickness of Type XHHW-2 rated for 90°C in wet or dry locations |
||
Ground |
•Bare copper concentric neutral surround the phase conductors |
||
Bedding |
•Glass-reinforced polyester tape bedding |
||
Jacket |
• Sunlight resistant Polyvinyl chloride (PVC) jacket |
TECHNICAL PARAMETER LIST
Size/ Construction (AWG or kcmil) |
Number of Strands |
Approxi. O.D. (mils) |
Approxi. Weight per 1000' (lbs) |
Allowable Ampacities |
||||
Phase Conductors |
Phase Conductors |
60°C |
75°C |
90°C |
Dwelling |
|||
SE-U Two Conductor with Bare Concentric Ground |
||||||||
8-8-8 |
7 |
8 |
587 X380 |
211 |
30 |
30 |
30 |
/ |
6-6-6 |
7 |
12 |
659 X 416 |
308 |
55 |
65 |
75 |
/ |
4-4-4 |
7 |
12 |
815 X 506 |
471 |
70 |
85 |
95 |
100 |
2-2-2 |
7 |
15 |
994 X 578 |
718 |
95 |
115 |
130 |
125 |
1-1-1 |
19 |
14 |
1093 X 664 |
904 |
110 |
130 |
150 |
150 |
2/0-2/0-2/0 |
19 |
18 |
1283 X 767 |
1379 |
145 |
175 |
195 |
200 |
4/0-4/0-4/0 |
19 |
18 |
1541 X 918 |
2146 |
195 |
230 |
260 |
250 |
NOTE: Other conductor sizes are available upon request.
CopyRight©2012-2013 Shanghai Morn Electric Equipment Co.,Ltd All Rights 沪ICP备2022033776号
Reserved Lingang factory address:
No.2829 Jiangshan Road, Pudong New Area, Shanghai, China
Tel:+86-21-68099820 Fax:+86-21-58975163