Stock Code:002451

中文版English

Secondary UD cable

Current Location:Home>Product> Secondary UD cable

Single URD cable

 600 Volt. Aluminum AlloyConductorCross-Linked Polyethylene (XLPE) Insulation Single Conductor Underground Service And Secondary Distribution Cable

APPLICATIONS

Secondary UD cable with single 1350-H19 Aluminum conductor suitable for use in underground service and secondary distribution, Secondary UD is permitted for 600 volt or less applications,either direct burial or in ducts.

STANDARDS

Secondary UD complies with the following:

ASTM B230,B231

UL 854

ICEA S-105-692

CONSTRUCTION

Conductor

Stranded compressed 1350-H19 aluminum

Insulation

cross-linked polyethylene (XLPE) insulation

TECHNICAL PARAMETER LIST

Code word

Size

(AWG or kcmil)

Number of

Strands

Insulation Thickness

(mils)

Nominal

O.D. (mils)

Approx.

Weight per

1000' (lbs)

Allowable Ampacity

Direct Burial

InDucts

Princeton

6

7

60

298

44

90

65

Mercer

4

7

60

345

63

120

85

Clemson

2

7

60

403

92

155

115

Kenyon

1

9

80

473

121

175

130

Harvard

1/0

9

80

512

146

200

150

Yale

2/0

11

80

555

177

225

170

Tufts

3/0

17

80

603

215

250

195

Beloit

4/0

18

80

658

263

290

225

Hofstra

250

26

95

732

315

320

250

Gonzaga

300

37

95

784

369

355

280

Rutgers

350

37

95

831

422

385

305

Emory

500

37

95

980

580

465

370

Duke

600

61

110

1086

699

510

410

Furman

700

61

110

1155

803

550

440

Sewanee

750

61

110

1188

854

580

470

Fordham

1000

61

110

1337

1109

670

545

Ampacity:90°C conductor temperature, 20°C ambient temperature, RHO factor 90, 100% load factor for three conductor triplexed.

 

 

NOTE: Other conductor sizes are available upon request.



CopyRight©2012-2013  Shanghai Morn Electric Equipment Co.,Ltd  All Rights  沪ICP备2022033776号
Reserved Lingang factory address:
No.2829 Jiangshan Road, Pudong New Area, Shanghai, China
Tel:+86-21-68099820  Fax:+86-21-58975163