600 Volt. Aluminum AlloyConductorCross-Linked Polyethylene (XLPE) Insulation Single Conductor Underground Service And Secondary Distribution Cable
APPLICATIONS
Secondary UD cable with single 1350-H19 Aluminum conductor suitable for use in underground service and secondary distribution, Secondary UD is permitted for 600 volt or less applications,either direct burial or in ducts.
STANDARDS
Secondary UD complies with the following:
•ASTM B230,B231
•UL 854
•ICEA S-105-692
•Stranded compressed 1350-H19 aluminum |
|
Insulation |
• cross-linked polyethylene (XLPE) insulation |
TECHNICAL PARAMETER LIST
Code word |
Size (AWG or kcmil) |
Number of Strands |
Insulation Thickness (mils) |
Nominal O.D. (mils) |
Approx. Weight per 1000' (lbs) |
Allowable Ampacity |
|
Direct Burial |
InDucts |
||||||
Princeton |
6 |
7 |
60 |
298 |
44 |
90 |
65 |
Mercer |
4 |
7 |
60 |
345 |
63 |
120 |
85 |
Clemson |
2 |
7 |
60 |
403 |
92 |
155 |
115 |
Kenyon |
1 |
9 |
80 |
473 |
121 |
175 |
130 |
Harvard |
1/0 |
9 |
80 |
512 |
146 |
200 |
150 |
Yale |
2/0 |
11 |
80 |
555 |
177 |
225 |
170 |
Tufts |
3/0 |
17 |
80 |
603 |
215 |
250 |
195 |
Beloit |
4/0 |
18 |
80 |
658 |
263 |
290 |
225 |
Hofstra |
250 |
26 |
95 |
732 |
315 |
320 |
250 |
Gonzaga |
300 |
37 |
95 |
784 |
369 |
355 |
280 |
Rutgers |
350 |
37 |
95 |
831 |
422 |
385 |
305 |
Emory |
500 |
37 |
95 |
980 |
580 |
465 |
370 |
Duke |
600 |
61 |
110 |
1086 |
699 |
510 |
410 |
Furman |
700 |
61 |
110 |
1155 |
803 |
550 |
440 |
Sewanee |
750 |
61 |
110 |
1188 |
854 |
580 |
470 |
Fordham |
1000 |
61 |
110 |
1337 |
1109 |
670 |
545 |
Ampacity:90°C conductor temperature, 20°C ambient temperature, RHO factor 90, 100% load factor for three conductor triplexed.
|
NOTE: Other conductor sizes are available upon request.